Thermoplastic PVC jacket with integral bonding wire 3/8" through 1-1/4"

Conduit shall be Anaconda SEALTITE® Type UA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 3/8" thru 4". Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors.

Specificationas

Tipo

N/A UA

Embalaje

N/A Las Cajas Pequeñas

Color

N/A Gris

Colores Opcionales

N/A Negro

Certificaciones

N/A
UL Listed & CSA Certified

Cross-Reference #

N/A 21101 55-08-26-03 6202-30-00 LA-11 UALT-1/2

Core Material

N/A Galvanized Steel

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 66/67

Jacket Material

N/A Polyvinyl Chloride (PVC)

Jacket Benefits

N/A Liquid Tight Oil Resistant

Instalación

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
  • Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 3/8" through 4".
  • Approved for direct burial and in concrete trade sizes 3/8" through 4".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

NEC Artículos

N/A

  • Equipo artículo 250.118 (6) Conexión a tierra
  • artículo 300.22 (D) Equipos de Tecnología de la Información
  • artículo 350 Liquid-Tight conducto metálico flexible (LFMC)
  • artículo 501.10 (B) (2) Clase I Div. 2 artículo
  • 502.10 (A) (2) y (B) (2) Div. Clase II. 1 y 2 del artículo
  • 503.10 (A) (3) y (B) Div. Clase III. Artículo 1 & 2
  • 620,21 Métodos de cableado Ascensor
  • artículo 645.5 (E) (2) En virtud de piso sobreelevado

Aplicación

N/A Where UL Listing is Required and Conduit Grounding is Necessary
Temperature Range: -40ºF to +176ºF (-40ºC to +80ºC)