LFNC tipo B conectores
flexible-wiring-conduits-fittings
-
Type A Nickel-Plated Brass Fittings for CNP (LFNC)
Construction
- Nickel-plated brass fitting with six-piece construction, consisting of a gland nut, TPE clamping ring, ferrule, body, seal inset into the body and insulated throat.
Description
- IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
- The fittings have superior pullout strength on Type CNP LFNC-A conduit, surpassing plastic fittings
- Halogen Free fittings
- Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
- The 90-degree fitting has a sweeping bore for easier wire pulling
- SEALTITE® Nickel-plated Brass Type A fittings installed on Type CNP conduit pass UL 514B pull tests
Applications
- Approved for both exposed and concealed locations
- Fitting for Non-metallic flexible conduit (LFNC-A)
- Meet NEMA FB-1 standard and UL 514B standard
- Suitable for Hazardous Locations per NEC Articles
- 501.10 (B) (2) Class I Div. 2
- 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
- 503.10 (A) (3) and (B) Class III Div. 1 & 2
Certifications
cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT
-
AISI-316 Compact Food Grade Fittings
These compact, stainless steel AISI-316 Food Grade fittings can be used with all ANACONDA SEALTITE® conduit, except for Type CNP, NMUA and NMEF.
The fitting design has round corners and a smooth profile to minimize risk of bacteria deposits and to promote cleaning. The fittings have excellent resistance to corrosion.
- Compliant with National Sanitation Foundation (NSF) requirements for liquid tight flexible conduit fittings for Food Zone Non-Contact and Splash Zone.
- Evaluated and in compliance with the current criteria for Hygienic Equipment Design of the EHEDG (report DTU CHD DR 2017 8037-088-3) locations.
- Special approvals per FDA guideline CFR21: Halogen free, TPE seals are formulated for food and beverage applications.
- Fittings have six parts (counter nut, upper seal, clamping ring, ferrule, body and 304SS locknut) providing for an IP 68 connection on approved conduit.
- Stainless steel AISI-316 fitting, consisting of six parts (counter nut, upper seal, clamping ring, ferrule, body and 304SS locknut)
- Hygienically designed with rounded corners and a smooth contourless profile to minimize the risk of bacteria deposits and to promote easy cleaning
- Evaluated and in compliance with the current criteria for Hygienic Equipment Design of the EHEDG (report .DTU CHD DR 2017 8037-088-3) locations
Specifications
- AISI-316 body with AISI-304 ferrule and counter nut, TPE clamping ring and locknut
- Color: Metallic
- Temperature range: -40º F to +221º F (-40º C to +105º C)
Applications
- Rated for Food Zone Non-Contact and Splash Zone applications
- For metallic flexible conduit
- Premium Stainless 316 for the best corrosion resistance
- Compact design for tight spaces
- Suitable for hazardous locations per NEC Articles
- 501.10 (B) (2) Class I Div. 2
- 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
- 503.10 (A) (3) and (B) Class III Div. 1 & 2
Certifications
cULus 514B Approved DWTT.E234207 / IP 68 rated according EN 60529, IP 69 rated according DIN 40050-9 (till 40 Bar high pressure) / NSF/ANSI 169
-
AISI-316 Stainless Steel Compact Fittings NPT
Construction
- 316 Stainless Steel fitting, has a four piece construction consisting of a gland nut, PA6 clamping ring, high tensile ferrule and body.
- Compact design is ideal for tight spaces: 20% smaller and 35% lighter than standard SEALTITE® fittings
- Superior Stainless Steel 316 corrosion resistance, strength and durability
- Halogen Free fittings
- IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
- Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
Applications
- Approved for both exposed and concealed locations
- Fitting for metallic flexible conduit
- Meet NEMA FB-1 standard and UL 514B standard
- Suitable for Hazardous Locations per NEC Articles
- 501.10 (B) (2) Class I Div. 2
- 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
- 503.10 (A) (3) and (B) Class III Div. 1 & 2
Certifications
cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT
-
Nickel Plated Brass Compact Fittings NPT
Construction
- Nickel plated brass fitting, has a four piece construction consisting of a gland nut, PA6 clamping ring, ferrule and body.
- Compact design is ideal for tight spaces: 20% smaller and 35% lighter than standard SEALTITE® fittings
- IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
- Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
Applications
- Approved for both exposed and concealed locations
- Fitting for metallic flexible conduit
- Halogen Free fittings
- Meet NEMA FB-1 standard and UL 514B standard
- Suitable for Hazardous Locations per NEC Articles
- 501.10 (B) (2) Class I Div. 2
- 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
- 503.10 (A) (3) and (B) Class III Div. 1 & 2
Certifications
cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT
-
Nickel Plated Brass Compact Fittings ISO
Construction
- Nickel plated brass fitting, has a four piece construction consisting of a gland nut, PA6 clamping ring, ferrule and body.
- Compact design is ideal for tight spaces: 20% smaller and 35% lighter than standard SEALTITE® fittings
- IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
- Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
Applications
- Approved for both exposed and concealed locations
- Fitting for metallic flexible conduit
- Meet NEMA FB-1 standard and UL 514B standard
- Suitable for Hazardous Locations per NEC Articles
- 501.10 (B) (2) Class I Div. 2
- 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
- 503.10 (A) (3) and (B) Class III Div. 1 & 2
Certifications
cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT
-
Zinc-Plated Steel Fittings
Construction
- Zinc-plated steel fitting, has a five piece construction consisting of a gland nut, sealing ring, high tensile grounding ferrule, insulated throat and body.
- IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
- Corrosion resistant, protecting from moisture and oil
- Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
Applications
- Approved for both exposed and concealed locations
- Fitting for metallic flexible conduit
- Meet NEMA FB-1 standard and UL 514B standard
- Suitable for Hazardous Locations per NEC Articles
- 501.10 (B) (2) Class I Div. 2
- 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
- 503.10 (A) (3) and (B) Class III Div. 1 & 2
Certifications
UL 514B TEOZ.E472179 / RoHS WEEE COMPLIANT
-
Type A CNP Zinc-plated Steel Fittings
Construction
- Zinc-plated steel fitting, has a 3 piece construction consisting of a two-piece gland nut, ferrule (PA6), and body
- Included sealing ring and galvanized steel lock nut
- Throat of the fitting has a plastic insulator
Installation
- Fitting is ideal for use with standard liquid tight non-metallic Type A conduit
- IP 67 Rated when installed with approved conduit
- Approved for both exposed and concealed locations
- Temperature range: -49ºF to + 221ºF (-45ºC to +105ºC)
- Suitable for use in hazardous locations per NEC Articles
- Article 501.10 (B) (2) Class I Div. 2
- Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
- Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
- Article 620.21 Elevator Wiring Methods
- Article 645.5 (E) (2) Under Raised Floors
Certifications
UL LISTED #E322120 / CSA Approved #620817 / RoHS WEEE COMPLIANT
-
Conectores NMUA Conectores de conductos no metálicos flexibles a prueba de líquidos (LFNC) Tipo B
Conectores NMUA Conectores de conductos no metálicos flexibles a prueba de líquidos (LFNC) Tipo B
(14)Construcción -Toda construcción de nylon tipo 66 viene con sello anular y tuerca de traba de acero incluidos - Los conectores reusables y duraderos son retardadores de llamas y resisten el agua salada, los ácidos ligeros, la gasolina, el alcohol, la grasa y los solventes comunes.
-
ATEX BXA AISI-316 Fittings
NOTE: SEALTITE® ATEX fittings are available for European or international applications. This product is not UL listed. This product is not approved for use in NEC Hazardous Locations.
Care must be taken when applying these to North American installations. The user is responsible for safe use and compliance with local regulations.Construction
- Stainless Steel Type 316 fitting, has a five piece construction consisting of a gland nut, sealing ring, high tensile grounding cone, barrier container and body
- A two-part compound epoxy seal is supplied to create the barrier
- Excellent corrosion resistance, strength and durability
Description
- Explosion Proof fittings for any SEALTITE® conduit (except CNP)
- IECEx-ATEX approved barrier fittings to provide seal around loose wires inside a SEALTITE® conduit
- A barrier around loose wires is created with a bi-compound epoxy seal supplied with each fitting
- IP 67 on the conduit and IP 66 between fitting and switchbox
- Excellent corrosion resistance with AISI-316 Stainless Steel
NOTE: For IECEx-ATEX applications, the fitting must be installed in pre-cut threads, without a locknut.
Specifications
- AISI-316 Stainless Steel with PTFE clamping ring
- Separate two-compound epoxy is provided for creating a barrier
- Color: Metallic
- Temperature range: -76°F to +266°F (-60°C to +130°C)
Applications
- Metallic flexible conduit
- Explosion-proof areas where Zone system used
- Machinery for export to other countries where Zone system used
- Superior corrosion resistance with 316 Stainless Steel
Certifications
IECEx-ATEX certified: CE0080 I M2 / II 2 GD / Ex d II C / Ex e II/ Ex d I / Ex tD A 21 IP 66
-
AISI-304 Stainless Steel Liquid Tight Fittings (NPT)
Construction
- Stainless steel (AISI-304) fitting, consisting of 4 parts (locknut, clamping ring, ferrule and body.)
- The counter nut and body are stainless steel (AISI-304). The ferrule is nickel plated brass. The clamping ring and insert are PA6.
- Included sealing washer and locknut provides a means for connecting the fitting to junction boxes
- IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
- Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
- Premium Stainless 304 for corrosion resistance
Applications
- Fittings for metallic flexible conduit
- Compact design for tight spaces
- Halogen Free
- Approved for both exposed and concealed locations
- Meet NEMA FB-1 standard and UL 514B standard
- Suitable for hazardous locations per NEC Articles
- 501.10 (B) (2) Class I Div. 2
- 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
- 503.10 (A) (3) and (B) Class III Div. 1 & 2
Certifications
cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT