Thermoplastic PVC jacket with integral bonding wire 1/2" through 1-1/4"

Conduit shall be Anaconda SEALTITE® Type CW. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 1/2" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 1/2" thru 3". Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors.
Unidad de medida

Specificationas

Tipo

N/A CW

Tamaño de campo eléctrico

N/A 3/4 in21 mm

Longitud

N/A 1000 ft304.8 m

Embalaje

N/A Estándar del Cartón

Diámetro Interior

N/A 0.820 to 0.840 in20.828 to 21.336 mm

Diámetro Exterior

N/A 1.030 to 1.050 in26.162 to 26.670 mm

Aprox. Dentro del Radio de Curvatura

N/A 5.0 in127 mm

Peso aprox. por 100 pies

N/A 44 lbs19.96 kg

Color

N/A Azul

Nota

N/A Otros colores disponibles bajo pedido.
3/8 "y 4" tamaños comerciales disponibles bajo pedido especial.

Certificaciones

N/A
UL Listed & CSA Certified

Cross-Reference #

N/A 221004 55-09-35-02 6403-66-00 CB CBLA-12 CBLT-3/4

Core Material

N/A Galvanized Steel

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 66/67

Jacket Material

N/A Polyvinyl Chloride (PVC)

Jacket Benefits

N/A Liquid Tight Oil Resistant

Instalación

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
  • Approved as an equipment grounding conductor in sizes 1/2" through 1-1/4, if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 1/2" through 3".
  • Approved for direct burial and in concrete trade sizes 1/2" through 3".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

NEC Artículos

N/A

  • Equipo artículo 250.118 (6) Conexión a tierra
  • artículo 300.22 (D) Equipos de Tecnología de la Información
  • artículo 350 Liquid-Tight conducto metálico flexible (LFMC)
  • artículo 501.10 (B) (2) Clase I Div. 2 artículo
  • 502.10 (A) (2) y (B) (2) Div. Clase II. 1 y 2 del artículo
  • 503.10 (A) (3) y (B) Div. Clase III. Artículo 1 & 2
  • 620,21 Métodos de cableado Ascensor
  • artículo 645.5 (E) (2) En virtud de piso sobreelevado

Aplicación

N/A Computer Wiring Meets Requirements of NEC
Temperature Range: -40°F to +176°F (-40°C to +80°C)